| Okanogan County Electric Co-op (OCEC)
OCEC is pleased to serve your electrical needs. An electrical
service Installation is a joint effort between you, your
building contractor, your electrical contractor, and OCEC.
An engineering fee of $75 is required in order to schedule a site visit and provide a cost estimate.
An OCEC Engineer will need the following information in order
to assist you with providing electric service to your project:
General Information
- Where the meter base will be located
- What the service will be used for (house, manufactured
home, RV, shop, irrigation, etc.)
- Type of service (Underground or Overhead)
- Service Size (200 Amp, 400 Amp, other)
- If possible, provide your legal address as determined
by the City or County Planning Office
The Engineer will provide you with additional information
depending on the type of service being installed
and the proximity of
your service to existing OCEC facilities.
A usable OCEC connection point on or near your
property will be necessary to provide electrical
service to
your project.
If an OCEC connection point is not within 300
feet of your project, a primary line extension may be
necessary.
|
|
CALL 811 @ LEAST 2 DAYS BEFORE YOU DIG
Primary wire: from existing facility to transformer, energized at 7200 volts.
Secondary wire: from transformer to meter, energized at 240 volts.
Service wire: from meter to panel, energized at 240 volts. |
|
Meter Base Location
Your meter base location must be approved by OCEC, accessible
for meter reading and maintenance, and for emergency personnel
to access in case of a fire.
The meter base must be located:
- Outside
- On a structure that is owned by you
- In an area not subject to being fenced in or enclosed
(patio, deck, carport, backyard)
- All meters must be mounted at least 5’ (five feet),
and not more than 7’ (seven feet), above final
grade
Note: Meter bases should not be enclosed. However, if you choose to enclose your
meter base, the enclosure must be accessible (for example,
install a hinged door so that no tools are required for access
to the entire panel) and meter face must be visible and unobstructed
to allow meter reads and maintenance.
Customer Responsibilities
- Contact
OCEC to obtain a cost estimate
- Call 811 at least 2 days before you dig
- Obtain an electrical permit, inspection and approval
from the Washington State Dept. of Labor & Industries
at 800/292-5920 or www.LnI.wa.gov
- Provide and install appropriate meter base, conduit,
and secondary conductor; leave wire coiled at the
base of the OCEC connection
point
- Expose the base of the existing facility, hand
digging when within 2’ of locate marks
- Return signed estimate paperwork with payment to OCEC
If applicable:
- Schedule
an inspection of your Primary Trench with OCEC
- Leave conduit ends capped; provide, but do not install,
sweeps at existing facility and/or proposed
transformer location
- Provide 6 yards of Bedding Sand at proposed
Transformer and/or junction-box (aka pedestal)
location
OCEC Responsibilities
- Determine the closest existing OCEC facility
- Provide a cost estimate
- Provide and install meter
- Connect customer-provided secondary wire at OCEC connection
point
If applicable:
- Provide
appropriate Easement Form(s)
- Obtain City, County, State, and/or Federal Agency Right-Of-Way
Permits
- Provide and install Transformer
- Provide and install Primary Wire
- Provide and install conduit for Primary riser on
OCEC pole
Recommended Trench Configuration
Minimum Requirements
12” seperation from telephone to any power line
Secondary = 2’ deep
Primary = 3’ deep

|
|